Product Description
Transmitters with remote transmission devices are suitable for the following situations
1. It is necessary to isolate the high-temperature medium from the transmitter.
2. The tested medium has a corrosive effect on the sensitive components of the transmitter
3. Suspended liquid or high viscosity medium
4. The tested medium solidifies or crystallizes due to changes in environment or process temperature
5. When replacing the measured medium, it is necessary to strictly purify the measuring head. The measuring head must be kept clean
technical parameter
Output:
Analog quantity: 2-wire system 4-20mADC
Digital quantity: Two wire system 4-20mADC and superimposed process variable digital signal that complies with the HART protocol.
Power supply: Supply voltage 12.5-45VDC
Load limit: The maximum load resistance Rmax of the circuit depends on the supply voltage. HART communication requires a load resistance of no less than 250 Ω and no more than 600 Ω
Communication distance:The maximum communication distance is 1.5Km, and multi station communication can connect up to 15 intelligent transmitters.
Output display:four digit digital display, five digit LCD display, pointer type.
Explosion proof form:
Intrinsically safe: ExiaII CT4
Flameproof type
Zero point transfer range:The zero point can be transferred positively or negatively at will, but the set measurement range upper and lower limits and range must not exceed the limit value.
Temperature range: Environmental temperature: -40~85 ℃ (-20~70 ℃ when using an LCD indicator)
Measurement medium temperature:
Remote device filling liquid (operating temperature):-40~104 ℃
Silicone oil: -29~+149 ℃
Inert oil: -18~+204 ℃
Pressure limit:
Thread type: 3.45Kpa (absolute pressure)~13.78MPa
Flange type: 3.45Kpa (absolute pressure) flange rated pressure
Plug-in type: 3.45Kpa (absolute pressure) flange rated pressure
Flat type: 3.45Kpa (absolute pressure) flange rated pressure
Relative humidity: 5-98% RH
Start time: 5 seconds to start
Capacity change: less than 0.16cm3
Damping adjustment: time 0.20-25 seconds
performance index
Reference conditions: Without migration, with a capillary length of 1.53m filled with silicone oil and a 316 stainless steel diaphragm
Temperature effect: Remote transmission device (typical case) with a capillary tube of 1.53m on one side (remote transmission device of the meter)
Flat type: The error is less than 0.62Kpa/55 ℃, and when using silicone oil filled capillary tubes, the error increases by 0.20Kpa for every 1.53 meter increase
Threaded and flange type: error less than 1.99Kpa/55 ℃, with an error increase of 0.62 Kpa for every 1.53 meter increase in silicone oil filled capillary tube used
Vibration impact: can withstand vibration with a frequency of up to 200Hz in any axis, resulting in an error of ± 0.05% URL
Power impact:less than 0.005%/V of the adjusted range
Load impact: No load impact
Installation position impact: Approximately 250Pa zero point migration, can be eliminated through calibration, without range effect